Pegler MVS is configurable for both HVAC and chilled systems
A Red or Blue indicator is visible to signify application
System Connection
Connectors suitable for system ends
MVS are available with factory fitted VSH XPress, VSH Tectite or Kuterlite adapters
H-Module
Recommend
Compact and economical 40 -120mm centres
Allows forward flushing where the system is flushed before letting water through the fan coil and control valve, clearing debris out of the inlet pipework
Allows reverse flushing where water flows backwards through the MVS and fan coil. Useful to flush debris out of a new fan coil unit without the risk of contaminating the control valve
Please Note:
BSRIA
Compliance to BSRIA BG 29/2012 drain arrangement
Additional pair of drains fitted between the MVS and the fan coil
Complies with BSRIA recommendations
Protects the entire MVS from contamination during flushing of the fan coil
Drain & Vent Option
A capped end can also be fitted with optional air vent or drain cock
Rotatable drain spigot for access from any angle
Manual air vent
Strainer
Recommended
Filters inlet flow protecting fan coil and control valve from debris
Includes 2 ball isolation valve so filter can be cleaned without draining system
Available in standard and extended handle variants
Test points are available as an optional extra to allow the strainer to be checked for blockages
Please Note:
If suitable separate strainers are fitted elsewhere in the system then the strainer can be omitted from the MVS assembly
PY always recommend that the PICV is protected by a strainer. Failure to do this can permanently damage the MVS
Control Valve
Any system over 50 fan coils we recommend the use of PICV
Comfort integration via Room Thermostat or Building Management System integration through range of actuators
PICV - 3 valves in 1 (Flow regulation, Pressure regulation, 2 port valve)
Venturi based flow measurement system (accurate to ±5%)
Pegler Proflow is unique as it can prove the flow rate
Smaller systems we recommend FODRV
Flow regulation, Flow isolation
Venturi based flow measurement system (accurate to ±5%)
Orifice based flow measurement system (accurate to ±10%)
Terminal Connection
The terminal connection installation can be variable from FCU centres and accessible for maintenance
Enables centres to be flexible from 40mm to 120mm
Pegler flexible connector option enable a direct fitment to a Fan coil without the need for further components
Please Note:
Factory fitted VSH XPress and VSH Tectite adaptors also available
Actuators for PICV
Actuators are also available with on/off and modulating options
Provides comfort integration via room thermostat or building management integration